Q.I have 4 drivers connected to a NETC02-CC. There is no problem with address number 0, but address number 1~3 cannot be controlled by remote I/O and set the operation data. What are the possible causes?

A.

Please check the setting of N-AXIS (RS-485 communication connection number setting switch) for NETC02-CC. If it is set to the initial value of "1," only address number 0 can be controlled and configured with remote I/O via CC-Link.
Change the setting according to the number of connections. (For 4 units, set to "4.")

N-AXIS (RS-485 communication connection number setting switch)

The N-AXIS setting status can be checked by the number of LED lights in the RS-485 LINK STATUS area on the front panel of the NETC02-CC. Please use these LEDs to confirm N-AXIS changes have been reflected.

  • [When N-AXIS is Set to "1"]
    When N-AXIS is set to
  • [When N-AXIS is Set to "4"]
    When N-AXIS is set to

Product Category: Controller and network compatible products
Model and Series: NETC02-CC
Description: Usage and setting methods, abnormalities and problems
FAQ No.: 460